Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM03468
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/15/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | Site Plan approval is required prior to building plan approval. |
| 07/16/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/18/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Separate toilet facilities is required for each sex. Reference section 2903.2 IBC. Revise plans 2. Provide elevations for accessible bathroom fixtures. 3. Second floor is required to be accessible unless exception #1 section 1104.4 IBC is used. Provide accessible route or define on plans proposed use, meeting criteria of exception #1. 4. Maneuvering clearances per section 404.2.4 ANSI 117.1 are not being met at rooms 207 & 208. Revise plans 5. An approval for deferred submittal from Building Official is required for steel joist. Submit a written request including approximate date of submittal to Dave Mann PE, Building Official. |
| 07/22/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Confirm that suspended water heaters comply with access requirements of Section 511.0, UPC 1994 with AZ State amendments. 2. Clarify termination of P-T Relief from water heater; detail 5/P3 notes two different locations. 3. The fixture, "RO," is not shown on the fixture schedule or fixture specifications. Include all fixtures when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994. 4. Based on the water calculations on sheet P3, the cold water to the water heater and the main hot water line are undersized. Please verify calculations and change sizing as required. 5. The site water meter and RPBP should be the same size. Reference Section 610.2, UPC 1994. 6. Provide CW shut off valve for building entrance. Reference Section 605.3, UPC 1994. 7. Show location and size of Water meter and RPBP on site plan. Reference Section 302.3, Uniform Administrative Code 1994. |
| 07/22/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. |
| 07/22/2003 | Robert Sherry | WATER | REVIEW | Approved | |
| 07/28/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Please submit calculations for lighting pole and lighting foundation. Over 20' pole needs structural review. 2. Landscape lighting on HP-12 not defined elsewhere. Please indicate fixture type and aprox location in plan view. |
| 07/31/2003 | DAVID RIVERA | ZONING | REVIEW | Denied | The building plans cannot be approved until the site plan has been approved. (The owner applied for a DSMR and was denied.) The site plan is out for corrections. |