Permit Number: T03CM03418
Parcel: 125071120

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T03CM03418
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
07/11/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
07/14/2003 GERRY KOZIOL WWM REVIEW Approved
07/14/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
08/07/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM03418

8/7/03 2742 E. 4th ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. PROVIDE A FOOTING UNDER THE WALL ON THE RIGHT SIDE OF SECTION B-B / A-8.

FLOOR PLANS:

1. PROVIDE LANDINGS AT DOORS 117E AND 118E. SEE R312.1.2 AND R312.2 .

2. PROVIDE HANDRAILS AT STAIRS WITH TWO OR MORE RISERS. SEE R315.1 AND R315.2 .

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

4. THE WALLS AND SOFFITS OF THE ENCLOSED SPACE UNDER STAIRS SHALL BE PROTECTED ON THE ENCLOSED
SIDE WITH ½" GYPSUM BOARD PER R314.8.

5. DETAIL AND SPECIFY STAIRWAY FRAMING CONNECTIONS.

SECTIONS - DETAILS - MISC. NOTES:

1. PLEASE CLARIFY THE BOTTOM TRACK TO WOOD CONNECTION. IF THE EDGE SCREWING IS FOR THE BOTTOM TRACK CONNECTION, PLEASE CLARIFY AND SPECIFY THE SCREW PATTERN.

2. 15 / A-10 ; PLEASE SPECIFY THE LEDGER BOLTS AND SPACING.

3. SHT. A-14 GYPSUM DRYWALL NOTES ; PLEASE SPECIFY SAG RESISTANT DRYWALL FOR CEILINGS IN ACCORD WITH TABLE R702.3.5 .





PLUMBING PLANS:

1. PLEASE CLARIFY THE DRAIN FOR THE CONDENSATE ON THE SOIL AND VENT RISER DIAGRAM. WET VENT WITHIN THE SAME STORY REQUIRES A 1 SIZE INCREASE OF THE VENT SIZE. PLEASE DON'T WET VENT BETWEEN STORIES.

MECHANICAL PLANS:

1. M-1 ; PLEASE IDENTIFY "AC-1" . DOES THE 12 X 8 RETURN AIR CONFORM TO M1602.2 ?


ELECTRICAL PLANS:

1. THE NEW BATH RECEPTACLES ARE REQUIRED TO BE ON A 20 AMP DEDICATED CIRCUIT.

2. IF THE TOP BETWEEN THE KITCHEN SINK AND THE RANGE IS 12" OR WIDER , IT REQUIRES A RECEPTACLE.
( SEE R3603.4 )

3. PLEASE NOTE , LIGHT FIXTURES ONER BATH TUBS AND SHOWERS ARE REQUIRED TO BE LISTED FOR USE IN WET AREAS.

4. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2003 LISA LESNY OUT TO CUSTOMER Completed