Permit Number: T03CM03414
Parcel: 136290020

Review Status: Completed

Review Details: 3RD PARTY REVIEW-CELL TOWER/ANTENNAS

Permit Number - T03CM03414
Review Name: 3RD PARTY REVIEW-CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q There is a reference to a 10 feet high chain link fence throughout the set that has a "chain link lid and metal slats". The design of this lid has not been presented in the set. Please provide a design for this "chain link fence lid", along with any structural calculations to support its design.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q The electrical one line diagram on Sheet E2 makes reference to Panel "A". The panel schedule on the same sheet is labeled Panel LP-1. Please coordinate.

-End of Review-