Permit Number: T03CM03388
Parcel: 137055220

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM03388
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-1
1. Provide door / door hardware and threshold specifications for the new exterior door. Ref. IBC 1003.3.1.6.

2. The signage exception referred to in the door schedule note 2 is applicable only to the primary entrance. Ref. IBC 1003.3.1.8.

3. Clarify how door 4 meets corridor requirement. Ref IBC 1004.3.2.5.

Sheet A-1.1
1. The toilet room finish schedule must provide surfaces as specified in IBC 1209.

STRUCTURAL COMMENTS
Sheet A-1
1. Please show a detail of the new opening at the main entry with design for new header / lintel and method of attachment to the new storefront.

PLUMBING COMMENTS - The plumbing portion has been reviewed and approved.

MECHANICAL COMMENTS
Sheet MP-2
1. Please revise plan and plan note M to indicate smoke detectors to be installed in return duct upstream of filters. Ref. IMC 606.

2. Indicate provisions for and point of termination for condensate disposal. Ref.
IMC 307.2.1.

ELECTRICAL COMMENTS
General
1. Existing panel schedule is noted as "TF" all circuit references are to Panel "A". Please clarify.
Sheet E-01
1. Coordinate with general comment 1.

Sheet E-02
1. Coordinate with general comment 1.

2. Show the additional exit light required on the sales floor side of the exit corridor at the rear of the store. Ref. IBC 1003.2.10.

3. The exit light within the corridor is shown on the night light circuit. Please clarify. It appears circuit A-10 should be described as exit and emergency lights.

4. It does not appear circuit A-2, described as shoe window lights was used. Please clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2003 ELAINE ROSE OUT TO CUSTOMER Completed