Review Details: REVISION - 2ND

Permit Number - T03CM03375
Review Name: REVISION - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise floor drains FD-4, and floor sink FS-3, and their trap arms as required to comply with Section 1003.3 and Table 10-1, UPC 1994 with AZ State amendments. Note: floor drain FD-4 (seven locations on P-4 and two locations on P-5) and floor sink FS-3 (two locations on P-4) are scheduled with 3" waste connections but are shown with 4" trap arms. The trap and the trap arm must be the same size.
2. Provide calculations to justify the gas pipe sizing. Clarify the gas load for K48. Reference Sections 1216.2 and 1216.3, UPC 1994.
3. Provide information to show how the cold water is used for hood K75C and why it requires only an atmospheric vacuum breaker while the hot water to the other hoods is protected with a reduced pressure backflow preventer. Please show this information on the drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2004 CINDY AGUILAR APPROVAL SHELF Completed
06/10/2004 CINDY AGUILAR OUT TO CUSTOMER Completed