Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03375
Parcel: 125100670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM03375
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2004 JIM TATE ENGINEERING REVIEW Denied Development plan approval is required.
03/26/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise floor drains FD-2 and FD-4, floor sink FS-3, and their trap arms as required to comply with Section 1003.3 and Table 10-1, UPC 1994 with AZ State amendments. Note: floor drains FD-2 and FD-4 along with floor sink FS-3 are scheduled with 3" waste connections on Sheet P-2. The trap and the trap arm must be the same size. Try relocating the fixtures.
2. Listing information supplied for the dishwasher, K-34, the potwasher, K-166, and the dishwasher B09 calls for a cross-connection device (a pressure vacuum breaker, atmospheric vacuum breaker, or a reduced pressure backflow preventer) to be installed at the water connection point. Please provide the required cross-connection device. Reference Section 603, UPC 1994.
3. Kitchen equipment K83, K86, and k117 are shown to have a 'Watts Series Cu7 Copper-body" double check valve on the Kitchen Equipment Schedule. Watts does not manufacture this model number; provide a listed cross connection control device. Reference Section 603, UPC 1994.
4. If the flood rim of the rotisserie, K96, is less than 1" below the water inlet, provide a cross connection control device. Reference Section 603, UPC 1994.
03/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/07/2004 EGRANT1 ZONING REVIEW Needs Review