Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM03375
Parcel: 125100670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM03375
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2004 JIM TATE ENGINEERING REVIEW Denied Development Plan approval is required.
02/20/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise floor drains FD-1 and FD-2, floor sink FS-1, and their trap arms as required to comply with Section 1003.3 and Table 10-1, UPC 1994 with AZ State amendments. Note: floor drains FD-1 and FD-2 along with floor sink FS-1 are scheduled with 2" waste connections on Sheet P-2. The trap and the trap arm must be the same size. Section 1003.3 allows the trap and trap arm to be increased by only one pipe size larger than listed in Table 7-3 to avoid losing the self-scouring action of the trap arm.
2. Comment not addressed. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
02/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not completely addressed. Provide signatures for ALL compliance sections of the energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1997.
2. Comment not addressed. Provide Listing information of the Type I hoods (1 - 7) to show that the exhaust volumes shown on the drawings are adequate for the intended applications. Reference Section 302.3, Uniform Administrative Code 1997. As stated on the submitted cut sheet for the Model CG3-BDL Hood: "The amount of exhaust volume required is dependent upon the type of cooking equipment and the type and volume of cooking. Refer to the Master Engineering Data Sheet in the Engineering Data section of the Gaylord catalog for the charts on determining exhaust volume, duct sizes, static pressure, water consumption, hot water requirements, and drain sizes."
3. Comment not completely addressed. Coordinate the revised hood information for K-93 (only one hood) with the equipment schedule shown on sheet M-1. Revise the Building Air Balance & Pressurization Data schedule to show only one hood.
4. Documentation not received with submittal. Provide listing information for EF-3. Reference Section 302.3, Uniform Administrative Code 1997.
03/03/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Approv-Cond Shop drawings to be reviewed and approved prior to installation
03/09/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
3/9/2004
The building plans may not be reveiwed and approved until copies of the approved development and landscape plans are included in each set of the building plans.
03/10/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
03/10/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2004 TAMI ACHONG OUT TO CUSTOMER Completed
03/11/2004 ANGIE SHOFFSTALL REJECT SHELF Completed