Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM03375
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. Provide complete site plan. Show location of all new/existing underground water mains. show location of all existing fire hydrants. 2. Provide complete fire sprinkler design criteria on plans. a. Standard to be used. b. Hazard Class(es). c. Minimum design density and area of application for each hazard class. d. Water supply information: Static psi, residual psi, flow gpm. |
| 07/16/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/16/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The enclosure for a grease duct serving a Type I hood (Detail 1/A-8.2) requires a minimum separation of 6" from the duct. Reference Section 506.3.11, IMC 2000. 2. Provide smoke detectors in the return ducts of all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC. 3. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 4. Provide energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1997. 5. Provide details demonstrating compliance of Type I exhaust terminations with Sections 506.3.3.3, 506.3.3.4, and 506.3.13, IMC 2000. 6. Provide hood for Double Deck Cook & Hold ovens (K54). Reference Section 507.2, IMC 2000. 7. Indicate location and size of hoods 8, 9, and 10 on floor plan. Reference Section 302.3, Uniform Administrative Code 1997. 8. Provide details and dimensions as required to show that the capacities of the Type I hoods (1 - 8) conform to the requirements of Section 507.13, IMC 2000 or are Listed with the exhaust volumes shown on the drawings. 9. Clarify the exhaust, make up air and HVAC systems in room 127 interact. Reference Section 302.3, Uniform Administrative Code 1997. 10. Provide ventilation for room 120 (Employee Break Room). Reference Section 401.2, IMC 2000. 11. Provide return or exhaust for rooms 116 and 117. Reference Section 403.1, IMC 2000. 12. Coordinate notes on Building Air Balance & Pressurization chart with the drawings. Reference Section 302.3, Uniform Administrative Code 1997. 13. Show airflow quantities for each diffuser or grille served by AC-7 (Service Yard). Reference Section 302.3, Uniform Administrative Code 1997. 14. Show airflow quantities for each terminal duct connection of AC-8 (Pre-conditioning). Reference Section 302.3, Uniform Administrative Code 1997. 15. Coordinate scheduled airflow capacity of AC-5 with the airflow quantities shown on the drawing. Reference Section 302.3, Uniform Administrative Code 1997. 16. All Type I and Type II kitchen exhaust hoods must be equipped with scrubbers. |
| 07/16/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Modify trap arm lengths to conform to Table 10-1, UPC 1994 with AZ State amendments. (3" trap arms have a maximum length of 6'-0") 2. The roof drain and overflow located near H.1- 3 on Sheet A-3.0 is approximately 18 feet from the corresponding roof drain shown on Sheet P-10. 3. Provide waste and vent isometrics. Reference Section 302.3, Uniform Administrative Code 1997. 4. Connection of kitchen equipment to a combination waste and vent system is not appropriate due to the potential for introducing grease into the drainpipes. Reference Section 910.0, UPC 1994. 5. An accessible cleanout is required in each vent of a combination waste and vent system. Reference Section 910.6, UPC 1994. 6. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. |
| 07/30/2003 | DAVID RIVERA | ZONING | REVIEW | Denied | Prior to Zoning approval of the building plans an approved development plan and landscape plan is required. Copies of both the development and landscape plans must be incorporated with the building plans set. As of this date 7/30/03 a development plan has not been submitted to the Development Services Department for review by CDRC. |
| 08/04/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Revise occupant load calculations to reflect fixed seating. Reference section 1003.2.2.9 IBC 2. Provide an exit plan including required widths and exiting for each area. reference sections 1003 and 1004 IBC 3. Allowable area calculations to be done in accordance with section 504 IBC. Revise calculations. 4. Grab bars for water closets indicate a height of 2' 0". Revise details 5. Provide van accessible parking space/ loading area including required signage. Reference section 1106.4 IBC 6. Door to remain open sign is not allowed in this use. Revise plans. Reference section 1003.3.1.8. 7. Posting of occupant load required in each assembly area. Reference section 1003.2.2.5 IBC. Show location and occupant load of each sign. 8. Provide listing for penetrations of firewall. 9. How is cross ventilation of attic space to be provided. Reference section 1202.2 IBC. 10. Platforms for the bench areas do not indicate the use of wood for the protection of decay and termites. Reference section 2304.11 IBC. Revise plans 11. Structural plans indicate design per UBC. Plans to be designed to the 2000 IBC. Revise plans. 12. Firpelace details reference UBC. Revise plans to comply with the IBC 2000 13. General foundation notes indicates 2500 psf soil bearing pressure to be used. Geotechnical report only allows 2000 12 " below grade. Please clarify. 14. Specify on plans structural panels to have a span rating of 32" o.c. 15. Clarify additional loads placed on roof system by stone veneer. See Section H sheet A-5.4. |
| 08/05/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. Sheet E-1 1. Keynote 10 refers to a sign. No such device on the Site Plan. Sheet E-2 1. "Feeder F" is actually the Service Entrance Conductors, and as such they should not have the 3/0 GND in each conduit, for that creates a parallel path for fault current on the line side of the MBJ. 2. Grounding Electrode Conductor is shown connected to the phase conductors on the line side of the Main CB. Please correct. 3. Ground Bus is shown connected to the phase conductors on the line side of the Main CB. Please correct. 4. Please specify sizing for the GEC and MJB. 5. According to Tucson Electric Power Service Requirements, AFC for a 1600A 208/120, pad mounted transformer service is 75,100 A. Please re-evaluate the 65K rating of service equipment, and at all other critical points of the system, or justify otherwise. 6. Panels A & F do not have AIC rating. Please indicate. 7. Panel D has MLO and L.O. CB. A "Lugs Only" CB? Please clarify. 8. Panels D, B & E have L.O. CBs. Please clarify. Sheet E-3 1. Provide 1998 IECC calculations for Interior Lighting Power Budget. 2. Could not find Keynote 2 on the plans. Is this #7? 3. Keynote 2 refers to Sheet E-10. There is no such Sheet. Is E-9 the intent? Sheet E-4 1. K166 is powered on A-13,15,17 on Power Plan. On Panel Schedule A-13,15,17 feeds K68. Please correct. 2. K168 on C-13 is listed as 30A on the Kitchen Equipment Schedule and is protected by a 30A CB. Yet the VA on the Panel Schedule is only 864 and the conductor is not sized for 30A. 3. It appears that K46, the 15A Hood, does not have power. 4. Please size the conductor for 30/1 CB on D-30,32. 5. K56 listed as 5 KW on Kitchen Equipment Schedule, but 600VA on E-26. Please clarify. 6. Size E-16,18, 20, 22 for 30A CBs, and in every other case where this applies. 7. It is unclear how K35, K75, K95 are being powered. Please clarify. 8. Receptacle on E-15 is not listed on Panel Schedule. Sheet E-5 1. Provide cut sheets for Fixture T, roof-mounted metal halide. Need to evaluate for compliance with the 1994 Lighting Ordinance. See http://www.ci.tucson.az.us/dsd/Outdoor_Lighting_Code.pdf. All fixtures over 50W shall be fully shielded. Also, it is unclear how the total watts on the Fixture Schedule Sheet E-7 could be 38 if the watts per lamp is 70. Corresponding circuits on Panel A could be overloaded. 2. Show panel and circuit number for EF-11, EF-9, EF-10 and EF-8. 3. AC-7 is shown as being powered by MSC-7. There is no MSC-7. On Line Diagram AC-7 is powered by MSB-17. Please clarify. 4. MAU-1 5 HP 208 V motor 16.7A per NEC Table 430-150. (16.7) (1.25) = 20.87. Please size the fuse at 20 A for overload protection or justify otherwise. 5. MAU-2 1 HP 208 V motor 4.6A per NEC Table 430-150. (4.6) (1.25) = 5.75. Please size the fuse at 6 A for overload protection or justify otherwise. 6. Provide maintenance receptacle within 25' of AC-6. 7. A-30 powers Rooftop GFI receptacles, but is listed as a Spare on Panel Schedule. Please correct. 8. AC-4 is shown as being powered by MSC-4. There is no MSC-4. On Line Diagram AC-4 is powered by MSB-14. Please clarify. 9. AC-3 is shown as being powered by MS-3. There is no MS-3. On Line Diagram AC-3 is powered by MSB-13. Please clarify. 10. AC-1 is shown as being powered by MSC-1. There is no MSC-1. On Line Diagram AC-1 is powered by MSB-11. Please clarify. 11. AC-6 is shown as being powered by MSC-6. There is no MSC-6. On Line Diagram AC-6 is powered by MSB-16. Please clarify. 12. AC-5 is shown as being powered by MSC-5. There is no MSC-5. On Line Diagram AC-5 is powered by MSC-15. Please clarify. 13. AC-2 is shown as being powered by MSC-2. There is no MSC-2. On Line Diagram AC-2 is powered by MSC-12. Please clarify. 14. REF-1 is shown as being powered by MSC-12. There is no MSC-12. On Line Diagram REF-1 is powered by MSB-10. Please clarify. 15. EF-6, EF-5, EF-4 and EF-2, at 1 1/2 HP 208 V motor 6.6A per NEC Table 430-150. (6.6) (1.25) = 8.25. Please size the fuse at 10 A for overload protection or justify otherwise. 16. EF-1 at 3/4 HP 208 V motor 3.5A per NEC Table 430-150. (3.5) (1.25) = 4.4. Please size the fuse at 6 A for overload protection or justify otherwise. 17. EF-3 at 2 HP 208 V motor 7.5 per NEC Table 430-150. (7.5) (1.25) = 9.4. Please size the fuse at 10 A for overload protection or justify otherwise. 18. AC-8 on Rooftop Electric and Mechanical Plans, but not on Mechanical Schedule. Can not evaluate feeder or overcurrent protection. Please coordinate with Mechanical. Sheet E-6 1. Can not find location of Panel CR, on this Sheet, or on Power Plan. 2. Show grounding per NEC 800-40. Sheet E-7 1. Detail B contains a reference to NEC 370-13. There is no NEC 370-13. Sheet E-8 1. Re-format specifications such that columns read right-to-left, please. Sheet E-9 1. Note 5 is inapplicable. City of Reno does not have jurisdiction here in Tucson, and plans ARE being submitted for approval with this review. |
| 08/06/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs to show location/method of connection to sewer |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/07/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 08/06/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |