Permit Number: T03CM03374
Parcel: 111084680

Address:
3625 E GRANT RD

Review Status: Completed

Review Details: SITE

Permit Number - T03CM03374
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2003 DAN CASTRO ZONING REVIEW Approved
10/03/2003 DAN CASTRO HANDICAP-SITE REVIEW Approved
10/06/2003 Blanca Espino ENGINEERING REVIEW Denied Site/Grading Plan
1. Indicate all proposed downspouts and or rain gutters. Roof drainage on sidewalks is unacceptable. Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10) year frequency flood events. D.S. 2-02.2.1.A.6 & D.S. 2-08.3.1 &4.0

2. Indicate existing and future sight visibility triangles for Far side (125') from PAAL onto Grant Road. 30' Pedestrian SVT's (Far side only) are applicable when medians exist. D.S. 2-02.2.1.A.10

3. Indicate a dimensioned detail of type, size and height of proposed signage on Site Plan. D.S. 2-02.2.1.A.13

4. New sidewalks on arterial streets are required to be 6' in width.
10/06/2003 BLANCA ESPINO SANITATION REVIEW Denied 1. Relocate refuse container location or loading space area due to inadequate maneuvering mobility. Demonstrated mobility area for refuse truck cannot overlap designated loading space area. For approval of proposed design, you may contact John Clark of Environmental Services at 791-3175 ext.1136
10/22/2003 JIM EGAN FIRE REVIEW Approved
10/28/2003 JOE LINVILLE NPPO REVIEW Denied Submit a Native Plant Preservation Plan or completed application for exception including the documentation listed in the instructions. Although an exemption letter was included with the submittal it was not signed or dated and does not include required additional information.
10/28/2003 Joseph Linville LANDSCAPE REVIEW Denied 1. A. Per LUC 3.7.3.2.A "Along interior lot lines of the site, the required perimeter screens must be located on the property line, unless the screen is provided between the property line and the use and a landscaped area of a minimum width of twenty (20) feet is provided between the screen and the property line". Revise the plans to locate the required screen wall on the property line or at an alternate location in compliance with the above section.

2) The retention basin in the northern part of the site is required to be landscaped per LUC 3.7.4.3.B and DS 10-01.0. Revise the plans to comply. At minimum, 20 trees per acre, two 5 gal shrubs per tree and groundcover plantings are required for the basin area.

3. A minimum of one tree for every thirty-three is required along the northern boundary of the site to comply with LUC Table 3.7.2-I.