07/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations per Section 403, IMC 2000. Show occupancy calculations on the drawing along with the occupancy classifications (from Table 403.3) used.
07/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The maximum GPM and Fixture Units for the 2" and 2-1/2" pipe sizes, as shown on the Water Piping Sizing Table (P-2) exceed the maximum velocity allowed for copper piping and also exceed the allowable pressure drop shown in your calculations.
2. Revise the water pipe sizes shown on the Hot & Cold Water Schematic to agree with your pipe sizing calculations.
3. The 2" main water line can handle 245 fixture units at 7.8 PSI/100FT. Show the total number of fixture units being served by this 2" pipe.