Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03337
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/29/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations per Section 403, IMC 2000. Show occupancy calculations on the drawing along with the occupancy classifications (from Table 403.3) used. |
07/29/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The maximum GPM and Fixture Units for the 2" and 2-1/2" pipe sizes, as shown on the Water Piping Sizing Table (P-2) exceed the maximum velocity allowed for copper piping and also exceed the allowable pressure drop shown in your calculations. 2. Revise the water pipe sizes shown on the Hot & Cold Water Schematic to agree with your pipe sizing calculations. 3. The 2" main water line can handle 245 fixture units at 7.8 PSI/100FT. Show the total number of fixture units being served by this 2" pipe. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/31/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
07/31/2003 | MONICA VALDEZ | REJECT SHELF | Completed |