Permit Number: T03CM03337
Parcel: 115062140

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03337
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2003 JIM EGAN FIRE REVIEW Approved
07/11/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide clean outs for all branches exceeeding 5' from main building drain: shower in room 106 and water closet in room 110.
2. Provide water pressure and pipe sizing calculations.
07/11/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
07/11/2003 ROBERT SHERRY WATER REVIEW Approved
07/11/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/11/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations per Section 403, IMC 2000.
2. Provide a minimum of 75 CFM exhaust per water closet. Reference Table 403-3, IMC 2000.
07/18/2003 GP BUILDING-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1.0
1. Please specify a smooth, hard, nonabsorbent surface, to a height of 4' for the walls within 2' of the water closets in rooms 111 and 112. Ref. IBC 1209.

2. Room 106 must be accessible unless intended for use by a single occupant. Ref. IBC 108.2


STRUCTURAL COMMENTS - The structural portion has been reviewed and approved.



PLUMBING COMMENTS - Plumbing portion has been reviewed by COT.

MECHANICAL COMMENTS - Mechanical portion has been reviewed by COT.

ELECTRICAL COMMENTS
General
1. Please coordinate with energy comment 1.

ENERGY COMMENTS
General
1. Please provide the interior lighting power analysis. Ref. IECC 705.4.
07/18/2003 GP ELECTRICAL-COMMERCIAL REVIEW Denied
07/25/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2003 ELAINE ROSE OUT TO CUSTOMER Completed