Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03318
Parcel: 117130990

Address:
420 S MAIN AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM03318
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 EROSE1 WWM REVIEW Needs Review
11/17/2003 ELAINE ROSE ZONING REVIEW Needs Review
11/17/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q Detail 3 on Sheet A4 needs to be dimensioned (and so does the plan view of the stair on Sheet A2). Specifically, what are the rise and run dimensions of the stairs, the width of the stairs, the landing dimensions [2000 IBC Sec. 1003.3.3.3 and 1003.3.3.4], and what are the horizontal and vertical dimensions of the handrails [2000 IBC Sec. 1003.3.3.11]? Please clarify.

STRUCTURAL:

q Provide a City of Tucson special inspection form for masonry [2000 IBC Chapter 17].

q Detail 3 on Sheet A4 shows steel in the stairs. What size is this steel? How often is it placed? Is there a minimum thickness for the concrete at the stairs? What size is the footing? The dimension of the steel lap? Please clarify.



-End of Review-
11/17/2003 EROSE1 WATER REVIEW Needs Review
11/17/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2003 ELAINE ROSE OUT TO CUSTOMER Completed