Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2003 GERRY KOZIOL WWM REVIEW Approved
11/14/2003 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM03286

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

4. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.

FOUNDATION PLANS:

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS,
OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS
NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF
THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE
CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS
RECOMMENDATIONS.

2. FOOTING WIDTHS FOR TWO-STORY, PER TABLE R403.1:

- 19" MINIMUM; CONVENTIONAL LIGHT FRAME
DETAIL 6/2 DID YOU MEAN TO USE 4/2?

3. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS
SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312. LANDING @ LAUNDRY ROOM?


FLOOR PLANS:

1. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.

- MAXIMUM SILL HEIGHT OF 44"

2. THE WALLS AND SOFFITS OF THE ENCLOSED SPACE UNDER STAIRS SHALL BE PROTECTED ON THE ENCLOSED
SIDE WITH ½" GYPSUM BOARD PER R314.8.

3. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 WITH MOISTURE RESISTANT GYP. BD.

4. NOTE AND SPECIFY THAT SHOWER ENCLOSURES SHALL HAVE A MINIMUM FINISHED INTERIOR OF 1,024 SQUARE INCHES AND SHALL BE CAPABLE OF ENCOMPASSING A MINIMUM 30" CIRCLE PER UPC SEC. 410.0. ALL GLASS ENCLOSURES SHALL BE TEMPERED.


5. DETAIL AND SPECIFY STAIR WIDTH (MINIMUM 36"), RISE AND RUN (MINIMUM 10" TREAD DEPTH AND 7 ¾"
MAXIMUM RISER HEIGHT PER R314), LANDING WIDTH (PER R312), HANDRAIL HEIGHTS (PER R315),
GUARDRAIL HEIGHT (PER R316) AND INTERMEDIATE RAIL SPACING (PER R316).

6. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.
MECHANICAL CHASE AT FIRST FLOOR?

STRUCTURAL PLANS:

1. PROVIDE STAIRWAY CONNECTION DETAILS AND STRINGER SIZES. PRE-FABRICATED METAL STAIR SHALL
HAVE MANUFACTURER'S SPECIFICATIONS ATTACHED TO PLANS.

ELEVATIONS:

1. INDICATE ALL MATERIALS USED; STUCCO - 1 COAT OR 3 COAT STUCCO? DETAILS CALL OUT BOTH?

2. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

3. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4.

PLUMBING PLANS: DRAWINGS SHOULD BE PER 1994 UNIFORM PLUMBING CODE WITH STATE AMENDMENTS.

1. PROVIDE AN ISOMETRIC DRAWING. 1ST FLOOR NOTE SHOULD BE 3" DRAIN DOWN WALL. 4" SEWER REQUIRED PROVIDE INFORMATION SHOWING THERE IS A EXISTING 4" SEWER LINE TO TIE INTO. MAKE SURE TIE-IN TO EXISTING SEWER IS SLOPED DOWN PER CODE. NEED TWO WAY CLEAN OUT WITHIN 2 FT. OF SEWER EXITING THE BUILDING. 2ND FLOOR MIN. 2" VTR FOR WATER CLOSET.

2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH. IT APPEARS WATER LINE AND METER ARE UNDERSIZED FOR ADDITION.

3. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER. CLEARLY INDICATE WATER HEATER IS ELECTRIC.

4. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. SHOW EXHAUST FAN LOCATIONS FOR BATHROOMS, WATER CLOSET COMPARTMENTS AND LAUNDRY ROOMS
IN LIEU OF OPERABLE WINDOWS, PER R303.3


ELECTRICAL PLANS:

1. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE
DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

2. LIGHT OVER BATH OR SHOWER MUST HAVE FIXTURES APPROVED FOR USE IN WET AREA.
PER IRC - E3903.8

3. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS. SERVICE GFCI OUTLET WITHIN 25 FT.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
CHRISTY FOREMAN @ 791-5550 EXT. 1113


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES.