Permit Number: T03CM03260
Parcel: 13811082A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03260
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2003 JIM EGAN FIRE REVIEW Approved
07/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Gas supply pipe to water heater appears to be undersized.
07/03/2003 ROBERT SHERRY WATER REVIEW Approved
07/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Duct enclosure for Type I hood (Sheet A3) does not meet current code requirements for clearances.
2. Provide sequence of control for exhaust fans and make up air systems.
07/08/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/09/2003 MVALDEZ1 WWM REVIEW Needs Review
07/09/2003 MVALDEZ1 ZONING REVIEW Needs Review
07/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE
07/09/2003 MVALDEZ1 ENGINEERING REVIEW Needs Review