Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03258
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The use of a 1" water meter will result in a water velocity in excess of 8 feet per second through the meter. Reference Section A 6.1, UPC 1994 and Section 610.0, IAPMO Installation Standards for Copper Pipe and Section 610.1, IAPMO Installation Standards for PVC Cold Water Building Supply and Yard Piping. 2. Show actual location of the water meter on the site plan. |
| 09/09/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The supply and return ducts for F2 and F3 are undersized. Reference Sections 1602.2 and 1603.1, IRC 2000. |
| 09/12/2003 | MELISSA POULIN | WWM | REVIEW | Denied | DEQ - Called 241-5329 to request design fee. Unable to leave message as mailbox was full. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 09/15/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |