Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The use of a 1" water meter will result in a water velocity in excess of 8 feet per second through the meter. Reference Section A 6.1, UPC 1994 and Section 610.0, IAPMO Installation Standards for Copper Pipe and Section 610.1, IAPMO Installation Standards for PVC Cold Water Building Supply and Yard Piping.
2. Show actual location of the water meter on the site plan.
09/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The supply and return ducts for F2 and F3 are undersized. Reference Sections 1602.2 and 1603.1, IRC 2000.
09/12/2003 MELISSA POULIN WWM REVIEW Denied DEQ - Called 241-5329 to request design fee. Unable to leave message as mailbox was full.