Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2003 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied 1. The supply and return ducts for F1, F2, and F3, are undersized. Reference Sections M1602.2 and M1603.1, IRC 2000.
2. The applicable code for all plumbing projects is the 1994 Uniform Plumbing Code with Arizona State Amendments.
3. Include the difference in elevation between the water meter and the highest fixture or water outlet in the water pressure calculations.
4. Include all of the water outlets in the fixture unit calculations (e.g. RO unit, icemaker, and pool fill. Reference Section 610.7 (1), UPC 1994.
5. Include the pressure drop of the RO unit in the water pressure calculations. Reference Section 610.2, UPC 1994.
6. Use Tables 6-3, 7-3, and A-2, UPC 1994, to calculate the number of fixture units in the project.
7. The use of a 1" water meter will result in a water velocity in excess of 8 feet per second through the meter. Reference Section A 6.1, UPC 1994 and Section 610.0, IAPMO Installation Standards for Copper Pipe.
8. Show actual location of the water meter on the site plan.
9. Provide exhaust for clothes dryer. Reference Section M1501, IRC 2000.
10. Based on the water pressure calculations shown, a ½" pipe can handle a maximum of 1 fixture unit. Confirm the sizes of branches serving 2 or more fixture units.
11. Provide drain for reject water from RO unit. Reference Section 304.0, UPC 1994.
12. Sign and seal the Compliance Statement for the energy conservation code calculations for the main house and the guesthouse.
13. Provide manufacturer's certified U-value for the windows used in the energy conservation code calculations. Reference Section 102.3, IECC 1998.
08/18/2003 GERRY KOZIOL WWM REVIEW Denied DEQ - Requested perc design/fee from Jake

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2003 TAMI ACHONG OUT TO CUSTOMER Completed
08/18/2003 ANGIE SHOFFSTALL REJECT SHELF Completed