Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM03220
Parcel: 140160110

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM03220
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide size of hood and required exhaust volume.
2. Provide size of duct to provide a minimum of 1500 FPM exhaust velocity.
3. Show how the make-up air quantity and the outside air provided by the existing rooftop air conditioners combine to meet the total exhaust volume and the requirements of Table 403-3, IMC 2000.
07/01/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide gas piping calculations and schematic drawing. Show total connected load, length of piping from the meter to the farthest outlet, and sizes of each pipe section.
2. Show all plumbing fixtures.
07/08/2003 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review