Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM03220
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/01/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide size of hood and required exhaust volume. 2. Provide size of duct to provide a minimum of 1500 FPM exhaust velocity. 3. Show how the make-up air quantity and the outside air provided by the existing rooftop air conditioners combine to meet the total exhaust volume and the requirements of Table 403-3, IMC 2000. |
07/01/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide gas piping calculations and schematic drawing. Show total connected load, length of piping from the meter to the farthest outlet, and sizes of each pipe section. 2. Show all plumbing fixtures. |
07/08/2003 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |