Permit Number: T03CM03159
Parcel: 11806071A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM03159
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2003 GERRY KOZIOL WWM REVIEW Approved
07/23/2003 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM03159

7/24/03 1973 W. SAN JUAN TRL.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. WATER HEATER T&P LINES ARE REQUIRED TO TERMINATE NOT LESS THAN 6" ABOVE GRADE.

STRUCTURAL PLANS:

1. THE 4X12 #1 D.F. APPEARS INADEQUATE OVER THE HALLWAY. PLEASE CHECK THE BEAMS AFFECTED BY THE OVER FRAMING.

SECTIONS - DETAILS - MISC. NOTES:

1. PLEASE PROVIDE ANCHOR BOLTS AT THE TOP OF THE MASONRY WALLS FOR THE PLATE. ARE THE ANCHOR BOLTS IN D-D/S4 TYPICAL ?

2. PLEASE SPEC THE FURRING'S BOTTOM PLATE AND IT'S CONNECTION TO THE SLAB.

3. DESCRIBE THE JOIST HANGER AT THE LEFT END OF THE TRUSS SHOWN IN SECTION D-D/S4.

4. 3/S4 ; AN 8" ANCHOR BOLT WON'T HAVE A MINIMUM 4" EMBEDMENT IN THE MASONRY FOUNDATION AFTER PASSING THROUGH THE FLOOR.

PLUMBING PLANS:

1. PLEASE PROVIDE A DETAIL FOR THE ISLAND VENT IN THE KITCHEN.

2. THE TERMINUS FOR THE WATER HEATER T&P LINE IS REQUIRED TOBE NOT LESS THAN 6" ABOVE GRADE.

ELECTRICAL PLANS:

1. PLEASE NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110