Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM03156
Parcel: 10511061R

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM03156
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1.1
1. The makeup air register shown at the grill area in the reflected ceiling plan is shown as a 24 x 24 supply register in the mechanical plan. Coordinate and clarify. The makeup air register shown in the kitchen area is not shown at all on the mechanical plan. Please coordinate and clarify.

Sheet A2
1. Elevations 1/A-2 through 4/A-2 are incorrectly noted as ¼" = 1'-0" scale. Note correct scale.

2. Dimension the tray slide height between the 28" minimum and 34" maximum allowed. Ref. ANSI A117.1, 904.4.

STRUCTURAL COMMENTS
General
1. Provide design calculations and detailed method of attachment for stainless steel mechanical hood equipment.


PLUMBING COMMENTS
Sheet P-2
1. The gas riser diagram shows an 1 ½" gas line to the BBQ griddle using 576 CFH at a developed length of 250'. It appears this should be a 2" gas line. Please revise. Ref. UPC Table 12-3.

MECHANICAL COMMENTS
Sheet M-2
1. The reflective ceiling plan shows 2 makeup air units. Only one is shown on the mechanical plan. Please coordinate and clarify.

Sheet M-3
1. Specify the two hour rating for the shaft detail 7/M-3.

2. Specify / detail through penetrations compliant with IBC 711.4.1.

ELECTRICAL COMMENTS
Sheet E1
1. Show the interlock for makeup air unit with EF-1 and EF-2. Ref. IMC 508.1.

Sheet E-2
1. Show the exit light and power provisions in coordination with the reflective ceiling plan.

2. Circuit A-8 for the VAV was not found on the power plan. Please clarify.

3. Coordinate with energy comment 1.

ENERGY COMMENTS
General
1. Provide the interior power lighting analysis. Ref. IECC Table 705.4.
08/20/2003 EROSE1 WWM REVIEW Needs Review
08/20/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2003 ELAINE ROSE OUT TO CUSTOMER Completed