Permit Number: T03CM03124
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM03124
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/25/2003 ROBERT SHERRY WATER REVIEW Approved
07/25/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
2. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 1994, as amended by the State of Arizona.
08/08/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/11/2003 GERRY KOZIOL WWM REVIEW Denied See previous comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
08/11/2003 ANGIE SHOFFSTALL REJECT SHELF Completed