Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03124
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/25/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. 2. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 1994, as amended by the State of Arizona. |
| 08/08/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/11/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | See previous comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/12/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 08/11/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |