Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM03124
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03124
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2003 GERRY KOZIOL WWM REVIEW Denied Needs credit evaluation - 8th floor - 740-6500
07/01/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete plumbing floor plan for project area. Reference Section 302.3, Uniform Administrative Code 1997.
2. The water riser diagram calls out a 1500-watt instantaneous water heater, the plumbing fixture schedule shows a 1300-watt hot water dispenser (in addition to a faucet for the lavatory), and the electrical plans indicate two 1000-watt water heaters. Please coordinate drawings. Reference Section 302.3, Uniform Administrative Code 1997.
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: www.azleg.state.az.us/. Reference Section 402.1, UPC 1994, as amended by the State of Arizona.
07/01/2003 ROBERT SHERRY WATER REVIEW Approved
07/01/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide reference documentation to show that the minimum quantity of outside air called for on sheet MP1.0 is provided by the main air handler.
07/11/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1- Hardwire WH cord connection is not acceptable.
2- Indicate Panel A.I.C. Rating.
07/15/2003 Raul Palma BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/24/2003 TAMI ACHONG OUT TO CUSTOMER Completed
07/16/2003 ANGIE SHOFFSTALL REJECT SHELF Completed