Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM03120
Parcel: 110055400

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03120
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2003 JIM EGAN FIRE REVIEW Approved
06/26/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Minimum pressure for plumbing fixtures must meet the manufacturer's recommended minimum pressure for the fixtures being installed.
2. Provide waste and vent diagram.
06/26/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
06/26/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Indicate components in plenum meet combustibility requirements shown in chapter 6, IMC 2000.
2. Provide statistical data to justify exception from using the occupant load shown in table 403-3, IMC 2000.
3. Provide smoke detector in return duct of AC-1.
06/27/2003 MVALDEZ1 ZONING REVIEW Needs Review
06/27/2003 MVALDEZ1 WWM REVIEW Needs Review
06/27/2003 MVALDEZ1 BUILDING-COMMERCIAL REVIEW Needs Review
06/27/2003 ROBERT SHERRY WATER REVIEW Approved
06/27/2003 MVALDEZ1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2003 MONICA VALDEZ OUT TO CUSTOMER Completed