Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03120
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/26/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Minimum pressure for plumbing fixtures must meet the manufacturer's recommended minimum pressure for the fixtures being installed. 2. Provide waste and vent diagram. |
| 06/26/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/26/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Indicate components in plenum meet combustibility requirements shown in chapter 6, IMC 2000. 2. Provide statistical data to justify exception from using the occupant load shown in table 403-3, IMC 2000. 3. Provide smoke detector in return duct of AC-1. |
| 06/27/2003 | MVALDEZ1 | ZONING | REVIEW | Needs Review | |
| 06/27/2003 | MVALDEZ1 | WWM | REVIEW | Needs Review | |
| 06/27/2003 | MVALDEZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/27/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/27/2003 | MVALDEZ1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/27/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |