Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03117
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning approval has been removed. 2nd kitchen not allowed and building is too high. PGehlen 12/29/2003 |
| 12/29/2003 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T03CM03117 - 2ND PLAN CHECK 12/29/03 4140 E. WAVERLY ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. PLEASE ADD THE ANCHOR BOLT AND THREADED ROD DETAIL TO THE PLAN. FLOOR PLANS: 1. INDICATE THE LOCATION OF THE TEMPERED GLASS ON THE PLAN. 2. THE BOOK CASES MAY BE INADEQUATE FOR REDUCTION OF THE WALL LENGTH. PROVIDE AN ENGINEER'S JUSTIFICATION OF THE ADEQUACY OF THESE BOOK CASES. STRUCTURAL PLANS: 1. THE ROOF LOADS ARE TO ACT ON THE CENTER OF THE WALL. PROVIDE AN ENGINEER'S JUSTIFICATION OF THE ROOF BEARING ASSEMBLY. PROVIDE THE CONNECTIONS. ELEVATIONS: 1. PLEASE NOTE ON THE PLANS THAT THE ROOF PANEL LAPS ARE TO HAVE SEAM SEALER. 2. INDICATE THE LOCATION OF TEMPERED GLASS. SECTIONS - DETAILS - MISC. NOTES: 1. PLEASE PROVIDE A CROSS SECTION OF THE FRAME WALL ABOVE THE STRAW BALE WALL TO STRAW BALE WALL CONNECTION. HOW IS THE KNEE ACTION OF THIS CONNECTION BRACED? PLEASE TALK TO ZONING ABOUT THE HEIGHT AND THE KITCHEN. 2. PROVIDE A CONNECTION FOR THE 2 X 6 RAFTER EXTENSIONS TO THE RAFTERS. 3. ILLUSTRATE THE MOISTURE PROTECTION ON THE PLANS. PLUMBING PLANS: 1.THE WATER HEATER IS NOT PERMITTED IN THE CLOSET UNLESS IT IS A DIRECT VENT WATER HEATER. 2. PROVIDE THE KITCHEN SINK PLUMBING ON THE PLAN. 3. VENT THE TUB. 4. THE AGGREGATE CROSS SECTIONAL AREA OF THE VENTS THROUGH THE ROOF IS REQUIRED TO EQUAL OR EXCEED THE CROSS SECTIONAL AREA OF THE REQUIRED BUILDING SEWER. 5. THE COMBUSTION AIR SHOULD BE IN ACCORD WITH THE STATE MODIFICATIONS TO THE U.P.C. ELECTRICAL PLANS: 1. PLEASE INDICATE THE CIRCUIT NUMBER FOR EACH DEVICE AT THE DEVICE. 2. PROVIDE ELECTRICAL LOAD CALCULATIONS PER THE I.R.C. 3. THE HEAT PUMP, 230 V. , REQUIRES TWO CIRCUITS. 4. CIRCUIT #7 APPEARS TO BE OVER LOADED. 5. DO YOU NEED A RECEPTACLE FOR THE RANGE? IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/30/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |