Permit Number: T03CM03111
Parcel: 10824013F

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T03CM03111
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2003 JIM EGAN FIRE REVIEW Approved
08/19/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 7/30/03:
1. It appears that electrical work consists of lighting. Without a fixture schedule this can not be determined. Note that lighting fixture schedule and cut sheets are a requirement for permitting.
2. It is unclear how these devices are to be attached. It looks like some are in parking spaces, some could be pole-mounted, some may be structure-mounted. Fixture schedule and cut sheets would tell a lot about this. In the case where a pole is to be installed, submit a pole detail. Submit structural calculations for the pole and foundation if the pole exceeds 20' in height.
3. Show routing of conduit to panels.
4. Show location of panelboards.
5. From the plan view it appears that the branch circuits are on Panel 10. Submit that panel schedule and its load calculations.
6. Specify conduit and counductor size and type.
09/10/2003 DAVE THOMAS BUILDING-COMMERCIAL REVIEW Approved
09/10/2003 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2003 LISA LESNY OUT TO CUSTOMER Completed