Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T03CM03111
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/19/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 7/30/03: 1. It appears that electrical work consists of lighting. Without a fixture schedule this can not be determined. Note that lighting fixture schedule and cut sheets are a requirement for permitting. 2. It is unclear how these devices are to be attached. It looks like some are in parking spaces, some could be pole-mounted, some may be structure-mounted. Fixture schedule and cut sheets would tell a lot about this. In the case where a pole is to be installed, submit a pole detail. Submit structural calculations for the pole and foundation if the pole exceeds 20' in height. 3. Show routing of conduit to panels. 4. Show location of panelboards. 5. From the plan view it appears that the branch circuits are on Panel 10. Submit that panel schedule and its load calculations. 6. Specify conduit and counductor size and type. |
| 09/10/2003 | DAVE THOMAS | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/10/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/10/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |