Permit Number: T03CM03068
Parcel: 114469370

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03068
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2003 JIM EGAN FIRE REVIEW Approved
06/24/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show plumbing pipe layout on the floor plan.
2. Provide a cleanouit for the new sink.
3. Provide water pressure calculations to verify pipe sizing.
06/24/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Need IECC calculations.
06/24/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculation.
2. Show existing and new ductwork on drawing.
3. Indicate air quantities for diffusers and exhaust fan.
06/24/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
07/21/2003 ROBERT SHERRY WATER REVIEW Approved
07/21/2003 DAN CASTRO ZONING REVIEW Approved
07/28/2003 GERRY KOZIOL WWM REVIEW Approved
07/28/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2003 TAMI ACHONG OUT TO CUSTOMER Completed