Permit Number: T03CM03039
Parcel: 11615194B

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM03039
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2004 EROSE1 FIRE REVIEW Stop
06/20/2003 ANY WWM REVIEW Stopped
06/20/2003 DAVID RIVERA ZONING REVIEW Approved
06/20/2003 ANY WATER REVIEW Stopped
06/20/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
06/23/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise Plumbing Fixture Schedule to conform to TAble 7-3, UPC 1994.
2. Confirm water pressure available to the project.
3. Resize waste and vent lines as required; Coordinate stack diagram and waste plan.
4. Show cleanouts on new building sewer.
5. Resolve conflicting gas loads for dryers.
6. Provide gas piping plan, including developed pipe length, total load at meter, and showing sizes of all pipe sections.
06/23/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
06/23/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide combustion/relief air for water heater.
2. Provide combustion/relief air for dryers.
3. Provide exhaust system for dryers that conforms to the manufacturer's recommendations and Section 504, IMC 2000.
4. Provide make-up air for dryers.
5. Provide ventilation calculations.
06/23/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied See attached.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2003 ANY APPROVAL SHELF Stopped
06/20/2003 ANY OUT TO CUSTOMER Stopped
06/20/2003 ANY REJECT SHELF Stopped