Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL TI
Permit Number - T03CM03039
Review Name: COMMERCIAL TI
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2004 | EROSE1 | FIRE | REVIEW | Stop | |
| 06/20/2003 | ANY | WWM | REVIEW | Stopped | |
| 06/20/2003 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/20/2003 | ANY | WATER | REVIEW | Stopped | |
| 06/20/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 06/23/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise Plumbing Fixture Schedule to conform to TAble 7-3, UPC 1994. 2. Confirm water pressure available to the project. 3. Resize waste and vent lines as required; Coordinate stack diagram and waste plan. 4. Show cleanouts on new building sewer. 5. Resolve conflicting gas loads for dryers. 6. Provide gas piping plan, including developed pipe length, total load at meter, and showing sizes of all pipe sections. |
| 06/23/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/23/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide combustion/relief air for water heater. 2. Provide combustion/relief air for dryers. 3. Provide exhaust system for dryers that conforms to the manufacturer's recommendations and Section 504, IMC 2000. 4. Provide make-up air for dryers. 5. Provide ventilation calculations. |
| 06/23/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See attached. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/20/2003 | ANY | APPROVAL SHELF | Stopped |
| 06/20/2003 | ANY | OUT TO CUSTOMER | Stopped |
| 06/20/2003 | ANY | REJECT SHELF | Stopped |