Permit Number: T03CM02966
Parcel: 128010090

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02966
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/02/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide permanent means of access to water heater located over 8'-0" above finished floor. Refer to Section 511.2, UPC 1994.
2. Provide complete plumbing drawings showing all drainage, vent, and water piping. Waste and vent diagram fot Toilet Room #4 is incomplete.
3. Provide water calculations to verify correct sizing of new water pipes.
4.Size the vents using Table 7-5, UPC 1994.
5. Automatic trap seal protection is required for floor drains. Reference Section 1007.0, UPC 1994.
07/02/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Exhaust discharge does not comply with Section 501.3, IMC 2000.
07/08/2003 MVALDEZ1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/08/2003 MONICA VALDEZ REJECT SHELF Completed