Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM02966
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/02/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/02/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide permanent means of access to water heater located over 8'-0" above finished floor. Refer to Section 511.2, UPC 1994. 2. Provide complete plumbing drawings showing all drainage, vent, and water piping. Waste and vent diagram fot Toilet Room #4 is incomplete. 3. Provide water calculations to verify correct sizing of new water pipes. 4.Size the vents using Table 7-5, UPC 1994. 5. Automatic trap seal protection is required for floor drains. Reference Section 1007.0, UPC 1994. |
07/02/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Exhaust discharge does not comply with Section 501.3, IMC 2000. |
07/08/2003 | MVALDEZ1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/08/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
07/08/2003 | MONICA VALDEZ | REJECT SHELF | Completed |