Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM02966
Parcel: 128010090

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM02966
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2003 JIM EGAN FIRE REVIEW Approved
06/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide permanent means of access to water heater located over 8'-0" above finished floor.
2. Provide complete plumbing drawings showing all drainage, vent, and water piping.
3. Provide water calculations to verify correct sizing of new water pipes.
4. Complete Fixture Connection Schedule on P1.2.
06/19/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/19/2003 ROBERT SHERRY WATER REVIEW Approved
06/19/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
06/19/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the restroom ventilation conforms to Section 401, IMC 2000.
06/19/2003 JIM TATE ENGINEERING REVIEW Approved
07/02/2003 MVALDEZ1 WWM REVIEW Needs Review
07/02/2003 MVALDEZ1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/02/2003 MONICA VALDEZ REJECT SHELF Completed