Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM02966
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/19/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
06/19/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide permanent means of access to water heater located over 8'-0" above finished floor. 2. Provide complete plumbing drawings showing all drainage, vent, and water piping. 3. Provide water calculations to verify correct sizing of new water pipes. 4. Complete Fixture Connection Schedule on P1.2. |
06/19/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/19/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/19/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
06/19/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the restroom ventilation conforms to Section 401, IMC 2000. |
06/19/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
07/02/2003 | MVALDEZ1 | WWM | REVIEW | Needs Review | |
07/02/2003 | MVALDEZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/02/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
07/02/2003 | MONICA VALDEZ | REJECT SHELF | Completed |