06/18/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide balancing data for the hood and the make-up air unit.
2. Show clearance dimentions for the exhaust fan and the make-up air unit. Reference Section 506, IMC 2000.
3. Provide structural calculations for the support of the hood.
4. Show new ductwork on drawing.
5. Provide ventilation calculations to demonstrate compliance with Section 403, IMC 2000.
06/18/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/18/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing design.
2. Provide calculations for modifications to natural gas distribution system.
06/20/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review