Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM02957
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide balancing data for the hood and the make-up air unit. 2. Show clearance dimentions for the exhaust fan and the make-up air unit. Reference Section 506, IMC 2000. 3. Provide structural calculations for the support of the hood. 4. Show new ductwork on drawing. 5. Provide ventilation calculations to demonstrate compliance with Section 403, IMC 2000. |
| 06/18/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/18/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing design. 2. Provide calculations for modifications to natural gas distribution system. |
| 06/20/2003 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |