Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM02934
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2003 | PIMA COUNTY | BUILDING-RESIDENTIAL | REVIEW | Denied | Electrical: 1) Please provide 2000 IRC grounding and bonding section numbers at service entrance diagrams. 2) 400 Amp service requires fault current documentation; i.e., "xx,xxx A.I.C. per Mr/Ms xxx xxxxx of power supplier on xx/xx/xx date. 3) Show wire sizes in panel schedules. 4) Note "GFI" at all outlets requiring compliance w/section 3802, 2000 IRC. 5. Provide room names on electrical floor plan. Mechanical: 1) Show/route/size flues for gas-fired equipment. 2. Verify combustion air. 3. Specify unit CFM floor plan distribution. CFM shall equal specified CFM. 4) Locate unit control thermostats. 5) Show/route/size gas flues. Plumbing: 1) Size domestic water main on site plan. 2) Route/note/size exterior sanitory drain on site plan. 3) Note CFH total demand at schedule and gas meter 4. Comply section P2903.9, 2000 IRC 5) Soil, waste and vent piping shall show compliance w/chapters 3031, 2000 IRC. |
| 07/14/2003 | CAGUILA1 | ZONING | REVIEW | Needs Review |