Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM02931
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1- Panel C on Panel Schedule is 100 A. On Line Diagram is 225 A. Please clarify. 2- Show load on new Panel C. 3- Provide overcurrent protection for new panel C and feeder. 4- Keynotes C & D disappeared on the revised plan. Please include. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/03/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |