Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM02931
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/02/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1- Panel C on Panel Schedule is 100 A. On Line Diagram is 225 A. Please clarify. 2- Show load on new Panel C. 3- Provide overcurrent protection for new panel C and feeder. 4- Keynotes C & D disappeared on the revised plan. Please include. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/03/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |