Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM02889
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/07/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations of heating and cooling loads to justify the 5-ton roof top air conditioner shown on detail 3/A1.2. Reference Section 703.2, IECC, 1998. Second request. Note: Section 703.2 requires the heating and cooling loads to be determined using the procedures shown in the ASHRAE Handbook of Fundamentals or an equivalent, approved method. Also, please resolve the conflict between the capacity of the air conditioner noted in Keynote 2, Detail 3/A1.0 and the air conditioner shown in Detail 3/A1.2 2. A plumbing vent is not an approved termination for a condensate drain from air conditioner. Reference Section 311.4, UPC 1994. |
08/28/2003 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/28/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 082703 In Panel A Load Calculations, 147.2 > 100 A. Panel CB is only rated for 100 amp. Bus rating not indicated on plans. If this is has a 100A main, it will be overloaded. |
08/29/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved |