Permit Number: T03CM02889
Parcel: 107142420

Address:
266 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02889
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations of heating and cooling loads to justify the 5-ton roof top air conditioner shown on detail 3/A1.2. Reference Section 703.2, IECC, 1998. Second request. Note: Section 703.2 requires the heating and cooling loads to be determined using the procedures shown in the ASHRAE Handbook of Fundamentals or an equivalent, approved method. Also, please resolve the conflict between the capacity of the air conditioner noted in Keynote 2, Detail 3/A1.0 and the air conditioner shown in Detail 3/A1.2
2. A plumbing vent is not an approved termination for a condensate drain from air conditioner. Reference Section 311.4, UPC 1994.
08/28/2003 Raul Palma BUILDING-COMMERCIAL REVIEW Approved
08/28/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 082703
In Panel A Load Calculations, 147.2 > 100 A. Panel CB is only rated for 100 amp. Bus rating not indicated on plans. If this is has a 100A main, it will be overloaded.
08/29/2003 PETER MCLAUGHLIN ZONING REVIEW Approved