Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM02808
Parcel: 12701008A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM02808
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2003 JIM EGAN FIRE REVIEW Approved
06/11/2003 GERRY KOZIOL WWM REVIEW Denied Needs to permit private sewer and shell bldg needs address. Needs grease interceptor.
06/12/2003 JIM TATE ENGINEERING REVIEW Denied A copy of the stamped approved Site Plan must be included in the submittal.
06/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide access to the water heater. Reference Section 511.2, UPC 1994.
2. Using the calculations shown on sheet P4 and Table 12-3, UPC 1994, the gas lines to WH and P7 appear to be undersized. Please confirm sizing.
3. Show size, routing, and termination point for temperature and pressure relief piping from water heater and storage tank on drawing.
4. Provide calculations showing water supply piping is sized in accordance with Section 610.5, UPC 1994. Include all fixtures when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994.
5. Indicate type of backflow prevention device to be used on each piece of equipment requiring backflow prevention.
6. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in Table 7-3, UPC 1994. Include the total number of each fixture being installed. Reference Section 302.3, Uniform Administrative Code 1997.
7. Provide upper terminal cleanouts on horizontal drainage pipe. Reference Section 707.4, UPC 1994.
06/19/2003 ROBERT SHERRY WATER REVIEW Approved
06/19/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Provide permanent means of access to the equipment located on the roof. Reference Section 306.5, IMC 2000.
06/27/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide calculations and curb details for proposed mechanical equipment on roof.
2. Provide structural calculations for soffit, glulam beam, and kitchen hood supported from roof trusses.
3. Code analysis data provided is incorrect. Appears to be utilizing early code edition. Revise plans and analysis sheet.
4. Main exit sign uses terminology from previous codes. Use current terminology as per section 1003.3.1.8.2 IBC.
07/01/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
7/1/2003
Copies of the stamped approved site/landscape plans must be included in each set of the building drawings prior to review and approval.
07/08/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E2
1. Locate equipment in Plan View that is to go on Panel "CC", by Panel & Circuit Number. None of the electrical loads appear to be fed from this panel.
2. There appears to be some "double counting" of loads on Panels "CC" and "K". For example, the Rice Warmers, at 600 VA each, are on K-25, 27 and CC-1,3. Please clarify.

Sheet E4
1. Not more than 42 overcurrent devices of a lighting and appliance panelboard shall be installed in any one cabinet or cutout box. See NEC 384-14 and 384-15. It appears from the plan view that this panel is in two separate enclosures, and the Panel Schedule itself denotes two sections, but please verify. Provide a cut sheet if necessary.
2. Load calculation for Panel "M" is suspect. For example, it feeds lighting dimmer Panel "L", yet there is no lighting listed in demand calcs; it lists Kitchen Equipment as 1,312 VA, yet it feeds Panel "K", which would have (20,145) (0.65) = 13,094 VA. Furthermore, the resultant for Panel "M" (218) should be the same as that calculated in the Building Electrical Service Load Summary (336.5). It is unclear which section of the Code is being used as the basis of these calculations. If it is Table 220-36, the 0.90 demand factor would be applied to the entire connected load, not a part of it. If it is Part B of NEC 220, I don't see where the 0.90 demand factor applies to HVAC and Refrigeration Equipment.
3. AFC at Panel "CC" is 15,348 per calculations. Yet the Panel, on Sheet E2, is only rated for 10,000A.

Sheet K1
1. Provide for a disconnect switch for the rooftop-mounted refrigerator compressor and any other such roof-mounted equipment.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2003 LISA LESNY OUT TO CUSTOMER Completed
07/09/2003 LISA LESNY REJECT SHELF Completed