Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM02765
Parcel: 11010298A

Address:
3150 N SWAN RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM02765
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2003 ROBERT SHERRY WATER REVIEW Approved
06/26/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet TS1
1. In the code data block, the governing fire code is the 2000 IFC. This was redlined so as not to require new approval signatures from TFD and COT floodplain reviewers.

Sheet A1
1. Please provide the item number from Table 719.1 (2) for the 1 hour fire resistive wall construction of the medical gas room or provide 1 hour fire resistive wall assembly number from an approved testing agency.

2. The 42" side grab bars are mislabeled as keynote 10.11. Please revise.



3. Specify skirting for the drinking fountain to comply with protruding objects provisions of ANSI A117.1,307.

4. Doors 202 and 206 may not utilize the exception provided in IBC 1003.3.1.8 for signage. This exception applies only to the main exterior door(s). Please see the 2000 IBC handbook - fire and life safety provisions attachment.

STRUCTURAL COMMENTS
General
1. Please provide a copy of the geotechnical report number 96268 by Pattison-Evanoff as referenced in the design calculations.

Sheet S2.0
1. The timber design calculations specify Douglas Fir-Larch number 2 for columns but the general structural notes specify a minimum of grade number 1. Please clarify.

2. Design shear wall 3 along line 3 from page 41 of the calculations is not shown on the plan. Please clarify.

3. The details referenced in the holdown schedule were not found in the plan set. Please provide.

Sheet S3.0
1. Please submit the engineered design prepared by an Arizona P.E. for the prefabricated jack, hip and girder trusses to be utilized in the high roof framing portion of the plan.

PLUMBING COMMENTS
Sheet P3
1. The fixture schedule indicates one floor sink. Two floor sinks are shown on the plan. Please revise fixture unit tabulations.

MECHANICAL COMMENTS
Sheet M1
1. Please revise general mechanical note 8 to indicate smoke detectors in return air systems in accordance with IMC 606.2.1.

2. The 12 x 8 transfer duct penetrates a one-hour fire resistive wall. Please specify a self closing smoke and draft assembly with a one-hour fire protection rating.






ELECTRICAL COMMENTS
Sheet E1
1. Please provide battery powered emergency lighting for the anesthetizing locations. Ref. NEC 517-63(a). If this requirement is met by the symbol denoted by keynote seven, please clarify. The symbol was not found in the legend.

Sheet E2
1. Circuits ISO 2, 6, and 8 were not found in the panel schedule. Please clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
06/27/2003 ELAINE ROSE ZONING REVIEW Needs Review
06/27/2003 EROSE1 WWM REVIEW Needs Review
06/27/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2003 ELAINE ROSE OUT TO CUSTOMER Completed