Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM02741
Parcel: Unknown

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM02741
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2003 DHERRON1 WWM REVIEW Needs Review
09/17/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied The second reviews for the above projects have been completed. This letter reflects comments, which need to be addressed by a written response to each, indicating action taken. In order to facilitate a shorter back-check time, we request that you please provide two (2) sets revised plans and calculations for each building type, highlighting any changes with appropriate revision numbers, revision date and "cloud bubbles." Please return redline drawings with your resubmittal.



Occupancy
Occup. Load
Construction
Area S.F.
Sprinklered
Alarms

Building type 1
R-2 /
Condominium

Building type II
28



_____
V-B, A.FS.



V-B AFES


Yes



Yes
Yes



Yes


GENERAL COMMENTS:

1. These projects have been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.

2. Under Arizona Statute, Title 33-1211, a recorded condominium document is required to create a condominium complex. Please provide intended condominium document with your resubmittal. Reference IBC Section 106. Please provide a copy of the recorded document.

3. The applicable drawing title blocks shall appropriately designate building #1. The City of Tucson Development Services requests that a separate contiguous set of plans be provided for each separate building permit required. Please comply. Reference IBC Section 106.1.1.





ACCESSIBILITY COMMENTS:

Sheet A2

1. All ground floor dwelling units that are not two-story dwelling units shall be shown to be accessible Type-B units or Type A units, as required. For development sites that have more than 20 dwelling units, 2% of the total dwelling units, but not less than one, shall be a Type-A accessible dwelling unit. Please review and designate Type-A and Type-B units on the construction site plan, and provide appropriate detail plans for Type-B accessible units and Type-A unit. A Type-A unit may be constructed in lieu of Type-B units. Reference IBC Section 1107.5.4.

2. All passage doors in a Type-B unit shall be accessible with not less than a 31.75-inch clear opening width. Type A requires not less than a 32-inch clear opening width. Coordinate door schedule. Reference IBC Section 1108, and ANSI 117.1, Sections 1002.5 and 1003.5.2.1.

3. The construction site plan shall clearly identify all required accessible routes. Reference IBC Section 1104.

4. Please provide appropriate details for accessible plumbing fixtures, storage, operable parts, windows, faucets, door hardware, counters, and other ADA components. Reference IBC Section 1108.
09/17/2003 DHERRON1 WATER REVIEW Needs Review
09/17/2003 DHERRON1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2003 DHERRON1 OUT TO CUSTOMER Completed