Permit Number: T03CM02675
Parcel: 114516940

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02675
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2003 PAUL MACHADO ENGINEERING REVIEW Approved An Elevation Certificate will be required prior to the issuance of a Certificate of Occupancy.
07/30/2003 David Rivera ZONING REVIEW Approved
07/31/2003 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM02675

8/4/03 8721 E. HONEY BEAR PL.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

3. LIST THE SQUARE FOOTAGES FOR ALL THE FOLLOWING AREAS SEPARATELY ON THE DRAWINGS:
- PORCH/PATIO COVERS

FLOOR PLAN:

1. PLEASE INDICATE WHICH WINDOWS ARE REQUIRED TO BE SAFETY GLASS.

2. COMPLY WITH R309.2. PROVIDE ½" GYPSUM BOARD ON ALL WALLS COMMON TO THE GARAGE AND HOUSE.
WHERE SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL
ALSO BE PROTECTED BY A MINIMUM ½" GYPSUM BOARD OR EQUIVALENT.

ELEVATIONS:

1. NOTE GLASS IN HAZARDOUS AREAS SHALL BE SAFETY GLASS PER R308.4.

SECTIONS - DETAILS - MISC. NOTES:

1. DTL. 3/10 ; PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLT.

2. DTL. 5/10 ; PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLT.

3. DTL. 7/10 ; SPECIFY THE PLATE MATERIAL ( PRESSURE TREATED, WOOD WITH A NATURAL RESISTANCE TO DECAY,….. ).

4. DTL. 10/10 ; HOW DOES THE LOG COMPLY WITH R323 ?

5. DTL. 10/10 ; PLEASE SPECIFY THE PIER MATERIAL AND TIES AT THE TOP.

6. DTL. 24/11 ; PLEASE PROVIDE FIRE BLOCKS AT THE CEILING LINE OF THE LOWER JOISTS.

7. FRAMING NOTE, ITEM 5, SHEET 11, AN 8" ANCTOR BOLT DOESN'T PROVIDE THE 7" OF EMBEDMENT REQUIRED BY R403.1.6 .

8. SECTIONS A, G&D/7 ; PLEASE PROVIDE CONNECTIONS FOR COFFERED CEILINGS.



PLUMBING PLANS:

1. PLEASE PROVIDE A DETAIL FOR THE ISLAND VENT.

2. PLUMBING FIXTURE SCHEDULE, SHT. 14 ; THE FIXTURE UNITS SHOULD BE IN ACCORD WITH THE U.P.C. (THE PLUMBING PORTION OF THE I.R.C. WAS NOT ADOPTED BY THE CITY. )

3. SIZE THE WATER SERVICE LINE AND WATER METER.

4. PLEASE CHECK THE 1" WATER LINE TO WATER HEATER #1 USING THE U.P.C. FIXTURE UNIT COUNT.

5. PLEASE SIZE THE WATER DISTRIBUTION BRANCHES.

MECHANICAL PLANS:

1. PLEASE SIZE THE RETURN AIR GRILL IN THE HALLWAY BY BEDROOM #3.

ELECTRICAL PLANS:

1. R3603.2 REQUIRES TWO 20 AMP CIRCUITS TO BE PROVIDED TO SERVE THE KITCHEN COUNTER TOPS.

2. R3603.4 REQUIRES A DEDICATED 20 AMP CIRCUIT TO SERVE THE BATHROOM RECEPTACLES.

3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

5. NOTE THE LIGHT FIXTURES IN THE SHOWER AND TUB AREAS ARE TO BE LISTED AS APPROVED FOR USE IN WET AREAS.

6. THE PANEL SCHEDULE LISTS THE WHIRL POOL RECEPTACLE AS A-5 BUT THE PLAN LISTS IT AS A-19.

7. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
08/04/2003 ANGIE SHOFFSTALL REJECT SHELF Completed