Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM02670
Parcel: 13340001B

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM02670
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2003 Loren Makus ENGINEERING REVIEW Needs Review
07/02/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet C.1
1. Site work note 6 references a soil bearing value of 1500 psf and states "see soils report". Please provide the soils report that was not included with the submittal package.

STRUCTURAL COMMENTS
Sheet A.1
1. Detail 2/A. indicates a footing schedule is to be referred to for steel reinforcement. No footing schedule has been shown. Please clarify.

Sheet A.2
1. Specify the post to beam connection at the entry patio detail 3/A.2.


2. Please coordinate roof assembly specifications between plan and design calculations. Calculations specify ½" oriented strand board which is not consistant with building section A/A.2. Also coordinate roof assembly notes as shown on the elevation drawings (Sheet A.3.).

Sheets A.2, M.1
1. Address concentrated loading of rooftop mechanical equipment shown on Sheet M.1 in the framing plan for the roof on Sheet A.2. Ref. IBC 1606.2.

PLUMBING COMMENTS
Sheet M.1
1. Coordinate with mechanical comment 3.

MECHANICAL COMMENTS
Sheet M.1
1. Please provide unit weight specifications for the rooftop mechanical equipment for coordination of structural comment regarding concentrated load.

2. Specify outside air provision. Ref. IMC 403.

3. Specify condensate material, size, slope and termination. Ref. IMC 307.

ELECTRICAL COMMENTS
Sheet E.1
1. The mechanical specifications for the package unit indicate a minimum 25 amp breaker is to be provided. Please coordinate with the electrical panel schedule which shows a 20 amp breaker.

ENERGY COMMENTS
Sheet E.1
1. Provide the interior lighting power analysis. Ref. IECC 705.4.
07/03/2003 ELAINE ROSE ZONING REVIEW Needs Review
07/03/2003 EROSE1 WWM REVIEW Needs Review
07/03/2003 EROSE1 FIRE REVIEW Needs Review
07/03/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2003 ELAINE ROSE OUT TO CUSTOMER Completed