Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM02625
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-1
1. Please coordinate wall sheathing and finish with structural design criteria. See structural comment 1, Sheet A1. Revise the details if necessary.

2. Provide a landing at the exterior door at the north side of the new addition. Ref. IBC 1003. Ref. IBC 1003.3.1.5.

3. Please clarify if the existing window in the south CMU wall is to be infilled or remain.

4. Please specify provisions for maintaining indoor temperature. Ref. IBC 1203.1.

5. Specify hardware for the egress door compliant with IBC 1003.3.1.8


STRUCTURAL COMMENTS
Sheet A-1
1. The exterior wall design loads assume 3/8" plywood with stucco finish. The plan details specify 5/8" T1-11 sheathing only. Please clarify.

MECHANICAL COMMENTS
Sheet A-1
1. Note provisions for combustion relief air for the existing gas fired water heater.

ELECTRICAL COMMENTS
Sheet A-1
1. Provide illumination at the exterior door at the north side of the addition. Ref. IBC 1003.2.11.

ENERGY COMMENTS
General
1. Please submit energy code data.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2003 ELAINE ROSE OUT TO CUSTOMER Completed