Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM02615
Parcel: 134234110

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02615
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-4
1. Please specify finish material in accordance with IBC 1209.2 for both walls adjacent to water closet.

STRUCTURAL COMMENTS
General
1. The deferred submittal of the mechanical hood, MH-1, must include load calculations, shop drawings and connections for approval prior to installation.

PLUMBING COMMENTS
Sheet P-3
1. Expansion tank notes specify Watts DET 12. The plan specifies Amtrol ST-5. Please coordinate.

2. Fixture connections indicate ½" HW to WC. Please revise.

3. A hose bibb is shown in the fixture connection schedule. This hose bibb was not found in the plan or isometric views. Please clarify.

4. Call out for the prep sink indirect waste to the floor sink is not shown in the waste isometric. Ref. UPC 801.

5. Please show indirect waste for the ice machine and walk in cooler in the isometric. Ref. UPC 801.

MECHANICAL COMMENTS
Sheet M-1
1. Please note that the mechanical hood, MH-1, is a deferred submittal and may not be installed prior to approval. Coordinate with structural general comment 1.

ELECTRICAL COMMENTS
Sheet E-1
1. The light and fan shown in the new bathroom are noted as existing and to remain. Please clarify.
07/18/2003 EROSE1 WWM REVIEW Needs Review
07/18/2003 EROSE1 FIRE REVIEW Needs Review
07/18/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2003 ELAINE ROSE OUT TO CUSTOMER Completed