Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM02601
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the natural gas pressure requirements on the drawings. Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide a natural gas regulator as required by manufacturer of the crematory and show on the drawing how the regulator and its associated piping is to be installed to conform to Section 1218.0, UPC 1994. |
| 08/11/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide Listing information for crematory in accordance with UL 791. Reference Section 907, IMC 2000. 2. Provide a detail of the installation of the hot air duct, including the termination of the duct. Show on the drawing how the duct is to be installed and terminated. Reference Section 302.3, Uniform Administrative Code, 1997. |
| 08/26/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/30/2003 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide available fault current and A.I.C. calculations. 2.#3 thhn cu. is not capable of carrying a 200 amp load.3. Gutter depth is greater than panel depth and encroaches into the dedicated working clearance. 4.Indicate the size of the grounding electrode conductor. 5.Provide the panels AIC rating. 6.Provide conduit and conductor sizes on all circuits. 7.Provide breaker size for cremater circuit. 8. Provide info on all lights and receptacles and show location on electrical floor plan.(outdoor lighting must comply with outdoor lighting ordinance). 9.AGAIN, see plan review "electrical requirements" . attached. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/02/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 09/02/2003 | MONICA VALDEZ | REJECT SHELF | Completed |