| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 7/1/2003 Copies of the stamped approved revised development and landscape plans must be included in each set of the building plans prior to review and approve. |
| 07/02/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Separate bathroom facilities required for each sex and each shall be accessible. Reference sections 2902.2 and 1108.2 IBC. Revise plans. 2. Bathroom doors do not meet maneuvering clearance for accessibility. Reference section 404.2.4 A117.1 ANSI. 3. Combustible construction is being specified. Not allowed in a Type IIB building unless complies with restrictions within exceptions. Reference section 603 IBC. Revise plans 4. Acoustical ceiling is not indicating carrying channels. Provide manufacturer specifications indicating compliance with ASTM C635 and C636. Also reflect criteria on plans. |