Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T03CM02575
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/12/2003 | TERRY STEVENS | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T03CM02575 07/12/03 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807. 2. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A CLEAR SPACE IN FRONT OF NOT LESS THAN 21" PER R307.2 (FIGURE). 3. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT. STRUCTURAL PLANS: 1. PROVIDE COMPLETE ROOF FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL LINTELS. 2. INDICATE WHAT FIREWALL FRAMING IS. [2X4@16"OC] ALSO INDICATE 5/8" TYPE X GWB ON BOTH SIDES OF WALL. ELEVATIONS: 1. NOTE LOCATION AND SIZE OF ALL VENTS NEEDED TO COMPLY FOR ATTIC VENTILATION.. SECTIONS - DETAILS - MISC. NOTES: 1. WOOD SILL PLATES FOR FUROUT SHALL BE FOUNDATION GRADE REDWOOD OR PRESSURE-TREATED WOOD PER R324. PLUMBING PLANS: 1. CROSS SECTIONAL AREA OF ROOF VENTING FOR WASTE LINES MUST EQUAL THE CROSS SECTIONAL AREA OF THE MAIN SEWER LINE. 2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH MECHANICAL PLANS: 1. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF 68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6. CLEARLY INDICATE WHAT THE FURNACE IS. 2. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.--------50 SQ. IN. IS NOT ADEQUATE FOR 110000 BTU'S-----MIN. IS 60 SQ. IN. EA COMB. AND REL. ELECTRICAL PLANS: 1. ONLY ONE CABLE DROP PER BLDG. IS ALLOWED FOR ELECTRIC SERVICES. INDICATE A DUAL PACK WILL BE INSTALLED NOT TWO SEPARATE SERVICES. NOTE THE GROUNDING AND BONDING METHOD. 2. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5. 3. NOTE THAT AT LEAST ONE 20-AMP BRANCH CIRCUIT SHALL BE INSTALLED TO SERVE THE LAUNDRY ROOM, AND THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS, PER E33603.3 AND 3801.8. 4. INDICATE THE LOCATION OF ELECTRICAL FOR FURNACE AND COOLER 5. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. -REQUIRED IN ALL BEDROOMS MODEL ENERGY CODE: 1. PROVIDE TWO COPIES OF ENERGY CALCULATIONS IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 1112 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 07/14/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |